{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

ADVC Controller Test and Training Set does not show the correct series

Issue
When the test and training set (TTS) is connected to the ADVC Controller it is showing a U-Series Recloser instead of a N-Series Recloser.

Product Line
ADVC II, Recloser, U-Series, N-Series, and W-Series

Environment
Testing the Recloser settings.

Cause
The old calibration files took the form of the first Recloser series that the TTS connects to.  The series cannot be changed after that.

Resolution
In order to have the TTS have the ability to switch between series the calibration file needs to be N24-150s (24kV 150kV BIL 1A CT's).
Attached is the calibration file, instructions on how to check the calibration file and how to load the file, and application notes about the calibration file.

Note:  The firmware of the ADVC Controller firmware must be A45-11.01 or above.

施耐德電機Taiwan

附件

SN392796.zipSN392796.zip [511 Bytes]
Schneider Reclosers ADVC Writing .cal file to TTS 1.0.pdfSchneider Reclosers ADVC Writing .cal file to TTS 1.0.pdf [300.92 KB]
Application Notes A45 multiple switch series TTS R03.pdfApplication Notes A45 multiple switch series TTS R03.pdf [24.63 KB]
探索更多
系列:
W-series ReclosersNulec N-seriesU-series Reclosers
產品:
990003000GCR_NULEC_RL27_KV
探索更多
系列:
W-series ReclosersNulec N-seriesU-series Reclosers
產品:
990003000GCR_NULEC_RL27_KV