我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to improve the online-build speed?
  • “General > Project autosaving on download” :  Uncheck the box "Save STU" \ "Save XVM
To secure application modification we recommend to Set “Save STA”.
  • "General > Management of build messages" : If the option “Multiple use of FB instances generates” is checked, the system control if all the DFB \ EFB instances are not used twice in the code and displays warning which impact the performance of the On line modification.
  • "General -> PLC embedded data" The option “Upload information” configured in the zone are embedded in the PLC after the transfer of the binary (Download), they consume memory in the program zone. The Upload information must be configured to authorize the Upload of the project (PLC -> Control Expert), they allow Control Expert to reconstruct the graphical part of the project when the Upload command is performed.
  • If the option “Upload information management” is in “Automatic” mode, at each On Line modification the Upload information are transferred automatically in the PLC.
To optimize the On Line modification the option must be put on “On user request” mode, the Upload information will be transferred manually in the PLC before the Off Line mode by the user (menu PLC -> Update upload information).
To secure application modification we recommend to set “Automatic mode”
  • "General > PLC embedded data" : Check “Optimize data on-line change” to  reduce the time of the Upload information generation relating to variables and function blocks of the project.
  • General > Management of Build messages: Turn off any warnings you don’t need.
  • General-> PLC diagnostics” : turn off application diagnostics, if not used.
  • “General-> PLC embedded data “ Uncheck  Data dictionary  if not needed  will reduce the amount of MB being sent by reducing the information on variables. DataDictionary is usefull for SCADA system or Vijeo Designer HMI.
    If need : Use the HMI Variable only, to reduce the number of variables.

施耐德電機Taiwan

附件
Capture.JPG.jpg [65.11 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings