What is the replacement for the Magelis XBTGT5330 HMI?

Issue
Magelis XBTGT5330 replacement

Product Line
Magelis

Cause
Obsolete product

Resolution
The Magelis XBTGT5330 HMI can be replaced by either the HMIGTO5310 or (HMIDT542 + HMIG3U). Here are details for the substitution replacements:

Substitution of XBTGT5330 to HMIGTO5310:
---VijeoDesigner applications are 100 % compatible
---The cut-out is identical.
---Screen resolution limited to VGA.
---The communication ports are identical except on COM1 , no RS422-RS485 signal only RS232C For RS422-RS485 link , use a cables with converter like TSXPCX1030 for Schneider Twido/Premium PLC or XBTZ980+XBTZG919 for Mitsubishi FX PLC
---Same certifications.
---No support of SoMachine PLC functions
---No extension Bus for Fieldbus modules ( Profibus , DeviceNet , CANopen )
---Only one USB port Host type A
---No auxiliary interface for speaker or alarm output
---Better Screen color TFT LED 65K , More Flash Memory , addition mini-USB Device port and use of SD card slot.

OR

Substitution of XBTGT5330 to HMIDT542 + HMIG3U
---VijeoDesigner applications are 100 % compatible.
---The cut-out is identical
---Screen resolution SVGA.
---The serial communication ports are identical but COM1 Subd9 RS422/R232C becomes the COM2 and the COM2 RJ45 RS485 becomes the COM1
---Ethernet port with higher speed and with a second port
---Same certifications.
---Possible Extension Bus for Fieldbus modules ( Profibus , DeviceNet , CANopen )
---No support of SoMachine PLC functions
---Same auxiliary interface for speaker or alarm output
---Better Screen color TFT LED 16M and more resolution , More Flash Memory , addition mini-USB Device + Host/Device front USB ports and use of SD card slot.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。