我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Unable to assign an IP address to a Unity Momentum processor using a Bootp or DHCP server
Issue
The purpose of this resolution is to inform users of the Unity Momentum processors that an issue exists when attempting to assign an IP address.

When a new 171CBU9809x is powered up, right out of the box, it does not send out any bootp requests.  After the PLC is powered on and it completes its boot up routine, the 'ETH STS' LED immediately blinks 6x (operating using default IP address).  Therefore, no IP was assigned via a bootp or DHCP server.  The only method to assign an IP address was to manually load a configuration to the PLC via USB with an IP address configured.

The issue occurs with 171CBU9809x firmware v.1.00 and v1.20.



Product Line
171CBU98090
171CBU98091


Resolution
The issue was resolved in firmware version 1.21.


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings