How many IFMs can be stacked to an IFE Switchboard Server (LV434011, LV434002)?
Issue:
End user would like to know how many IFM (Modbus Interface Modules) can be connected to a single IFE (Ethernet Interface) using the Stacking Connector (TRV00217).
Product Line:
IFE and IFM devices
Environment:
Modbus Communications
Cause:
It is possible to connect multiple IFM's to a single IFE
Resolution:
Twelve (12) IFMs can be stacked to an IFE Switchboard Server (LV434011) via the stacking connector. To find out more information about the stacking connecter please check out FA374688. Note: The LV43011 is obsolete as of Oct. 8th, 2021. Recommended replacement is the LV434002.