我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to manage Data inconsistencies in DDDT type of Advantys equipments used in Unity Pro?

Goals and Symptoms

On some equipment, you can have inconsistencies between data in the DDDT type of Advantys equipment when used in Unity Pro.

Example: STB AHI 8321 Module used in an STB island with STB NIP 2x 1x module.
Image1

Causes and Fixes

This behavior is normal If the data is not 32-bit aligned that means, if the Primary variable (32 bit data) object is not acquiring addresses like 0,4,8,12 etc...then the M580 master aligns them automatically to the Byte array. So it is necessary to plan the island in such a way that the variables falls at a 32-bit boundary.

Another easier solution consists in Configuration Advantys software for each module to add an alignment parameter, this parameter allows to re-align the variables.
Image2

After validation variables become consistent.
Image3


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings