What are the difference between TIME and LTIME data types in Machine Expert?
Issue:
What are the difference between TIME and LTIME data types in Machine Expert?
Product Line:
Machine Expert
Resolution:
TIME is a 32 bit data type. The resolution is in milliseconds.
LTIME is a 64 bit data type. The resolution in nanoseconds.
Example of variable declarations:
var_0 AT %MD0: TIME; // %MD0 overlaps with %MW0 and %MW1
var_1 AT %MD1: TIME; // %MD1 overlaps with %MW2 and %MW3
var_2 AT %ML0: LTIME; // %ML0 overlaps with %MW0, %MW1, %MW2 and %MW3
var_3 AT %ML1: LTIME; // %ML1 overlaps with %MW4, %MW5, %MW6 and %MW7
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.