Trio Q & J Radio Multi-Use Serial Port Wiring

Overview

Both the Trio Q and Trio J radios have a multi-use serial port. Each radio features a 9 pin miniature D-Shell (DE-9) female connector that supports two individual serial port connections.

Typical use case for the J (unlicensed 900Mhz/2.4Ghz) or Q (licensed 150Mhz/450Mhz) radios will be Ethernet communications. Yet for legacy applications, a Modbus Gateway (Modbus TCP to RTU protocol converter), or Modbus Serial Device Server (Modbus RTU in TCP) may be configured on the serial port. A serial port may also be configured as a TUI (Text User Interface) for configuration/diagnostics. The TUI diagnostics is useful on systems suffering from high error rates as it provides a basic high speed interface.

Serial port configuration is accomplished with a web browser and the default IP address of both radios is 192.168.2.15. Details of how to configure each radio’s serial port for your application can be found in the Q or J radio documentation installed with TVew+.

Serial Port A & B (J series Radio)

Data Port A uses pins 2 & 3 with pin 5 as the common ground*
Data Port B uses pins 4 & 6 with pin 5 as the common ground*

Serial port pinout

RS-232 Mode
PinNameInput / Output
1Not Used---
2Port A RxDOutput
3Port A TxDInput
4Port B TxD (Diags)Input
5GND---
6Port B RxD (Diags)Output
7Not Used---
8Not Used---
9RSSI / General Purpose PinOutput



* There is no option for RS-485 connections with the J Series radio.

COM Port 1 & 2  (Q series Radio)

COM 1 uses pins 2,3,7 & 8 with pin 5 as the common ground
COM 2 uses pins 4 & 6 with pin 5 as the common ground

serial port DB9

RS-232 ModeRS-485 Mode
PinNameInput / OutputNameInput / Output
1COM 1 DCDOutputNot Used---
2COM 1 RxDOutputB / Z (Inverting)Input / Output
3COM 1 TxDInputA / Y (Non-Inverting)Input / Output
4COM 2 TxDInputNot Used---
5GND---Not Used---
6COM 2 RxDOutputNot Used---
7COM 1 RTSInputNot Used---
8COM 1 CTSOutputNot Used---
9RSSIOutputRSSIOutput



施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings