我们今天能为您提供什么帮助?

What is the maximum number of events for the BMXERT1604 buffer

Issue
The user manual does not state what the maximum nuber of events that the buffer in a BMXERT1604T can hold.

Product Line
BMXERT1604T

Environment
Windows 10

Resolution
The maximum buffer size is (16 events x 255 groups max)= 4080 events.

Each group can have a maximum of 16 events.

Events with the same timestamp will be packed into one (1) group.

If the buffer is filled, it will take 204 CPU scans to clear it.

Note: Because only the events with same time stamps will be packed in one group, the 4080 maximum number of evens in the buffer may never be reached.





施耐德電機Taiwan

探索更多

系列:

探索更多

系列:

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。