PME 8.0/8.1 - Designer crashes when attempting to open a 3300 ACM meter

Issue
When attempting to open a 3300 ACM in Designer to configure the meter, the system prompts the following error and results in a crash.

ACM Error in Designer

Product Line

330 ACM Meter
Power Monitoring Expert 8.0

Power Monitoring Expert 8.1

Environment
Power Monitoring Expert Designer Application

Cause
Designer crashes as a result of the ACM 3300 meter returning "330" for its Device type rather than "3300".

Resolution
**Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
A patch is available to resolve this issue within Designer. (set3300.zip attached below)
To deploy this patch, please perform the following:

  • Make a backup copy of set3300.dat, which you will find in the following folder: <PME installation folder>\system\etc
    • E.g. C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc\set3300.dat
  • Copy the new version of set3300.dat over top of the original version.

Alternatively, as a workaround you may use ION Setup to perform the meter configuration. (The latest version of ION Setup can be obtained from FA212816)
*It is expected that support for the 3300 in Designer will be phased out in a future software release.

施耐德電機Taiwan

附件
set3300.zip [5.53 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings