What are the Modbus Function Codes supported by the new UNITY Momentum controllers?

Issue:

What are the Modbus Function Codes supported by the new UNITY Momentum controllers?

Product Line:

Unity, Momentum, Quantum, M580, M340

Resolution:

Modbus function codes supported by the Unity Momentum Controller:

  • 01 = Read multiple bits (%Q)
  • 02 = Read multiple discrete bits (%I)
  • 03 = Read multiple words (%MW)
  • 04 = Read multiple input words (%IW)
  • 05 = Write single bit (%Q)
  • 06 = Write single words (%MW)
  • 07 = Read Exception Status (For serial line only)
  • 08 = Diagnostic with the following sub-functions attached for serial line only:
    • Sub-function code 00 “echo mode" (Return Query Data)
    • Sub-function code 01 (Restart Communication Option)
    • Sub-function code 02 (Return Diagnostic Register)
    • Sub-function code 03 (Change ASCII Input Delimiter)
    • Sub-function code 04 (Force Listen Only Mode)
    • Sub-function code 10 (Clear Counters and Diagnostic Register)
    • Sub-function code 11 "counter 1" (Return Bus Message Count)
    • Sub-function code 12 "counter 2" (Return Bus Communication Error Count)
    • Sub-function code 13 "counter 3" (Return Bus Exception Error Count)
    • Sub-function code 16 "counter 6" (Return Slave NAK Count)
    • Sub-function code 17 "counter 7" (Return Slave Busy Count)
    • Sub-function code 18 "counter 8" (Return Bus Character Overrun Count)
  • 11 = Get Com Event Counter (For serial line only)
  • 12 = Get Com Event Log (For serial line only
  • 15 = Write multiple bits (%Q)
  • 16 = Write multiple words (%MW)
  • 22 = Mask write register (As a Server only)
  • 23 = Read/Write multiple registers (%MW)

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings