How is a dynamic braking resistor added to an ATV32 drive?
Issue:
Addition of dynamic braking resistor on ATV32.
Product Line:
Altivar 32
Environment:
All
Cause:
N/A
Resolution:
Wiring:
The resistor should be wired to the PA and PB terminals on the drive.
Programming:
DRI- > CONF > FULL > FUN- > STT
Go into CONF menu, then FULL menu, then FUN menu.
Under FUN, go into STT- menu.
Set brA to [No].
Addition of dynamic braking resistor on ATV32.
Product Line:
Altivar 32
Environment:
All
Cause:
N/A
Resolution:
Wiring:
The resistor should be wired to the PA and PB terminals on the drive.
Programming:
DRI- > CONF > FULL > FUN- > STT
Go into CONF menu, then FULL menu, then FUN menu.
Under FUN, go into STT- menu.
Set brA to [No].