Video: Why does the Local/Remote button not work on the Process drive keypad?

Article available in these languages: 芬蘭文

Issue:
Local/Remote button does not work

Product line:
Altivar 600 Family: ATV630, ATV650, ATV660, ATV680
Altivar 900 Family: ATV930, ATV950, ATV960, ATV980

Environment:
All

Cause:
Default programming

Resolution:
The factory setting for Process drives' Local/Remote button is 'deactivated'.
To activate it:
  1. go to menu 5: Complete Settings (CSt-)
  2. go to menu 5.5 for ATV600: menu 5.4 for ATV900: Command and Reference (CrP)
  3. go to parameter HMI cmd. (bMP) and change it from Deactivated (diS) to Bumpless (buMP) or to Stop.
Bumpless means that if transitioning from Remote to Local the drive will continue in it's last state...so if it was running, it will continue to run at the same speed, but can now be controlled by the keypad in local mode.  When changing from local back to remote the drive will only run if the remote controls are calling for it to run and it will automatically switch to the remote speed reference.
Stop means that the drive will be stopped when switching between Local and Remote and a new run command will be required.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings