我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: How do I reset a Process Drive to factory settings?

Article available in these languages: 芬蘭文, 日文

Issue:
Process Drive reset to factory settings

Product Line:
ATV6xx, ATV9xx

Environment:
All models and serial numbers

Cause:
Need to factory reset the drive

Resolution:
1. From the main menu, scroll down to menu 7 [File Management], press OK
2. Scroll down to menu 7.2 [Factory Settings], press OK
3. Scroll down to [Parameter group list], press OK
4. Select from the following list depending on what parameters you want to reset.  Select "All" for factory reset of all parameters.
- [All] ALL
All parameters in all menus.
- [Drive Configuration] drM
Load [Complete settings] CSt- menu.
- [Motor Param] MOt
Load [Motor parameters] MPA- menu.
- [Comm. Menu] COM
Load [Communication] COM- menu.
This parameter can be accessed if [Config. Source] FCSI is set to [Macro-Conf] ini.
[Display Config.] dIS
Load [Display screen type] MSC- menu.
This parameter can be accessed if [Config. Source] FCSI is set to [Macro-Conf] ini.

5. Press ESC to go back to the previous menu
6. Highlight "Go to Factory Settings" and press OK.  You will get the following screen:

*****************************************************************************************************************************
WARNING

UNANTICIPATED EQUIPMENT OPERATION
Verify that restoring the factory settings is compatible with the type of wiring used.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
******************************************************************************************************************************

7. If the above warning is observed, then press OK to return the drive to factory settings.


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings