What causes Err9 fault on the ATV212 Drive?
Issue:
Err9 fault on ATV212
Product Line:
Altivar 212
Environment:
All
Cause:
Fault code
Resolution:
This fault will appear if the remote graphic keypad is used for control and the cable gets disconnected. This is if CMOd = 1 or FMOd = 3.
Check that the cable is still connected and not loose.
Check the keypad for issues or try another keypad.
Check for electrical noise.