我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
When upgrading Control Expert (formerly Unity Pro) will I lose my projects?

Issue:

When upgrading Control Expert (formerly Unity Pro) will I lose my projects?


Product Line:

Control Expert, Unity Pro

Resolution:

No, you will not lose your projects  However you should create a temporary folder on your hard drive and conduct a search for *.STU, *.STA  *.XEF & *.ZEF .
You should have an STA and ZEF for each of your applications. Move the results of each of these four searches to the temporary folder. Once Control Expert has been
upgraded you can select Tools/Option and change the PATH to where Unity will store project files.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings