我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Why is the meaning of the red I/O LED ON on a M241 controller?

The red I/O LED indicates device errors on the serial line 1 or 2, SD card, cartridge, TM4 bus, TM3 bus.

For example, only the fact that serial line 1 or 2 is not connected or the SD card is not present will turn the I/O LED ON but everything else may work correctly.

To find out exactly why the LED is turned on, you can check the PLC_R structure in a Watch window, specifically PLC_R.i_lwSystemFault_1

Bit field FFFF FFFF FFFF FFFF hex indicates no detected error.
A bit at low level means that an error has been detected:
- bit 0 = Reserved
- bit 1 = TM3 detected error
- bit 2 = Ethernet IF1 detected error
- bit 3 = Ethernet IF2 detected error
- bit 4 = Serial 1 in overcurrent detected error
- bit 5 = Reserved
- bit 6 = CAN 1 detected error
- bit 7 = Reserved
- bit 8 = Reserved
- bit 9 = TM4 detected error
- bit 10 = SD Card detected error
- bit 11 = Firewall detected error
- bit 12 = DHCP server error detected
- bit 13 = OPC UA server error detected

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings