What causes E-17 fault on an ATV21 / ATV212 series drive?
Issue:
E-17 fault code is displayed on ATV21 / ATV212 drives

Product Line:
Altivar ATV21 and ATV212 series drives

Resolution:
E-17 is displayed on the ATV21 / ATV212 series drives when a button on the keypad is held down for more than 20 seconds.
If no button is being held down, then this could be a stuck key. Attempt to free a stuck button by powering down the drive and repeatedly pressing/releasing all keypad buttons.

This could also be an electrical problem with the switch where it is making contact when it is not being pressed, or possibly a problem with the microprocessor that thinks the button is being pressed when it is not.

As there are very few replacement parts for the ATV212 series, and none for the ATV21 series, replacement of the entire drive is often necessary to correct this problem.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings