What are the "watts losses" or heat dissipation ratings for the ATV660 series drives?

Issue:
Needs the "watts loss" or heat dissipation ratings for the ATV660 series drives.

Product Line:
ATV660 enclosed Altivar Process Drives

Environment:
All models, all serial numbers

Cause:
Customer was unable to find information in current literature.

Resolution:
This information can be found in the user manual for the ATV660 series drive, Doc NHA91297 .
See attached file.


Input and Output Current Ratings and Dissipated Heat, Normal Duty Operation

VacRatingDrive RatingFull Load Input Current (A)Full Load Output Current (A)Full Load Bypass Current (A)Typical Dissipated Power at Rated Load (W)
hpkW
23010.7U072.64.64.263
21.5U15586.8100
32.2U227.211.29.6138
53U4012.918.715.2226
7.55.5U5517.125.422289
107.5U7522.832.728401
1511D1132.946.842651
2015D1545.563.454768
2518D1854.578.468860
3022D2264.392.680972
4030D3088.61231041231
5037D37107.81491301553
6045D45130.41751541789
20810.7U0734.64.669.93
21.5U155.987.5111
32.2U228.411.210.6153.18
53U401518.716.7250.86
7.55.5U552025.424.2320.79
107.5U752732.730.8445.11
1511D113946.846.2722.61
2015D155363.459.4852.48
2518D186778.474.8954.6
3022D227692.6881078.92
4030D301051231141366.41
46010.7U071.32.22.160
21.5U152.643.484
32.2U223.85.64.8115
53U406.79.37.6173
7.55.5U559.112.710231
107.5U7511.916.514272
1511D111723.521378
2015D1523.331.727515
2518D1828.939.234680
3022D2234.446.340739
4030D3045.961.552898
5037D3757.374.5651072
6045D4569.188771324
7555D5584.2106961418
10075D75112.71451241823
12590D90135.81731562120
150110C111952111802530
200130C132322502403150
250160C162773023024030
300200C20349370*4380
400250C25432477*5750
500310C31538590*7810
600400C40681730*9900
700500C50846900*13330
900630C6310581140*16250

施耐德電機Taiwan

附件
ATV660 Power Dissipation.pdf [43.04 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings