Control a Vijeo Designer HMI panel navigation using a SoMachine PLC

Issue:
How to Control a Vijeo Designer HMI panel navigation using a SoMachine PLC

Product Line
Vijeo Designer, SoMachine, EcoStruxure Machine Expert

Resolution:
To control the panel displayed on a Vijeo Designer HMI from a SoMachine PLC,
1) Start by creating a SoMachine variable of type INT and share it with Vijeo Designer through the Symbol Configuration.
In our example, the INT variable is called "iPanelNumber" from the POU called "PanelControl":
Variable Sharing of INT in Symbol Configuration Node

2) Once this is done, you should link this shared variable to an internal variable in Vijeo Designer called _CurPanelID
- Select _CurPanelID from the Variables pane.
- Assign the Variable from SoMachine "_SoM.MyController.Application.PANELCONTROL.iPanelNumber" to the "Read From Variable" row of the Property Inspector
_CurPanelID Read Variable from PLC location in Vijeo Designer

This method is also viable in EcoStruxure Machine Expert.

Attached is a Sample Project created in SoMachine v4.3 Patch 2 with Vijeo Designer v6.2.6.1 update installed:
"ReadFromVariableToCurPanelIDExample.project"

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

附件
ReadFromVariableToCurPanelIDExample.project [521.17 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings