How do I access the Com Scanner Input and Output tables on the Altivar Process Drive?

Article available in these languages: 芬蘭文

Issue:
Access the Comm Scanner Input and Output tables on the Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
To configure the Comm. Scanner (Input/Output) tables:

Resolution:
Programming from the Drive:

  • [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner input]
    • Up to 8 input registers can be configured
    • By default the first 2 registers are pre-configured
      • [Scan. IN1 address] nMA1 - 3201 (EtA Status word)
      • [Scan. IN2 address] nMA2 - 8604 (rFrd - Output frequency)
  • [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner output]
    • Up to 8 output registers can be configured
    • By default the first 2 registers are pre-configured
      • [Scan.Out1 address] nCA1 - 8501(CMd word)
      • [Scan.Out2 address] nCA2 - 8602(LFrd - Output freq in rpm)




Programming from Somove:

  • [Parameter List] [Fieldbus] [Port - Modbus Serial] [Modbus Fieldbus]

screenshot

NOTE: This is not the same as the I/O scanning table that is used with Ethernet communications.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings