我们今天能为您提供什么帮助?

Where Can I Find SCCR and Short-Circuit Protection Information for ATV320 Drives?

Article available in these languages:

Resolution:
The SCCR ratings and short-circuit protection requirements for the Altivar Machine ATV320 are provided in document NVE21777.

This document includes information such as:

  • SCCR ratings
  • Approved fuse recommendations
  • Approved circuit breaker recommendations
  • Short-circuit protection requirements
  • Installation and compliance guidance

The document can be downloaded from the Schneider Electric website:

ATV320 Getting Started Annex (SCCR)

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)



施耐德電機Taiwan

探索更多

系列:

探索更多

系列:

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。