我们今天能为您提供什么帮助?

The Trend graph is not updating on the Magelis Runtime. How resolve the issue?

Issue:
The Trend graph is not updating on the Magelis Runtime.  How resolve the issue?

Product Line:
HMIGTO/GTU/STO/STU, XBTGC/GK/GT, iPC

Resolution:
It is possible that there are too many files in the storage drive.  It is recommended to format the storage device and redownload to the Magelis target.  On project download, please make sure to check the checkbox to  "Delete All Runtime Data".

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。