Power Monitoring Expert Error "Missing Template" When Clicking on the Settings Link in the Web Applications
Issue
Unable to view the settings in the Web Applications
Product Line
Power Monitoring Expert 8.0
Environment
Power Monitoring Expert 8.0 systems in which the default/Web path was changed to something else for the installation.
Cause
GeneralSettingsDialog.js file does not get updated for systems that are not using a web URL path other than default /Web.
Resolution
1) Navigate to the installation directory (i.e. C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\) and then "...\Applications\ApplicationFramework\content\"
2) Open the file "GeneralSettingsDialog.js" using a text editor (eg. Notepad, Notepad++)
3) Change line 25 so that the virtual path is correct. Example of the default path: " TemplateUtil.LocAndLoad('/Web/Content/GeneralSettingsDialog.html', new Core.CallBack(function (templateText) {"
- If the path to the Web Applications is servername\pme line 25 would need changed to: "TemplateUtil.LocAndLoad('/pme/Content/GeneralSettingsDialog.html', new Core.CallBack(function (templateText) {")
發佈於: 施耐德電機Taiwan


需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。