我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: How can you turn off the flashing red caution LED on the ATV630 and ATV930 process drives?
Issue:
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.

Product Line:
Altivar ATV630 and ATV930

Environment:
All

Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.

Resolution:
The warning LED is triggered when a Warning Group item is activated.  The factory default has many items selected for monitoring under Warning Group 1.  A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.



From the Main menu:
  1. Scroll to Complete Settings and press OK
  2. Select Error Warning Handling and press OK
  3. Select Warnings Group Configuration and press OK
  4. Select Warn group 1 definition and press OK
  5. Now (almost halfway down the list) uncheck "AI1 4-20 Warning", "AI2 4-20 Warning", and "AI3 4- 20 Warning" boxes.


See attachment

Now the red flashing warning light will turn off.

施耐德電機Taiwan

附件
ATV630 Warning groups.png [52.65 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings