我们今天能为您提供什么帮助?
Video: How do I adjust the position of my Multi-Turn Absolute Encoder motor with Lexium 32?
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
發佈於: 施耐德電機Taiwan