What is the 'Manual Setting Requrie Reset' field in the Ethernet Diagnostics DTM window.
Answer
Issue
What is the purpose of the 'Manual Setting Require Reset' field' in the Ethernet Diagnostics DTM window?

Product Line
BMENOC301, BMENOC0311

Environment
Windows 10, Unity

Resolution
The DTM Ethernet Diagnostics window for the 'BMENOC03xx' shows a line labeled 'Manual Settings Require Reset'.  the Unity help does not provide enough information about the displayed message returned by the module.

This text field has two possible values for each Ethernet port:

  • If there is an Ethernet link on that port, then the message reads: “Devices require a reset service to be issued to its Identity object in order for the changes to take effect”
  • If there is no Ethernet link on that port, then the message reads: “Interface can activate changes to link parameters automatically”

ee


This text refers to the behavior of the CIP TCP/IP Interface object, class code 0x5F. This CIP object is used if you want to manually change the IP parameters of the device/port (IP address, duplex, baudrate, etc). If the port has a link when you change the parameters, you have to issue a soft reset to the module in order to apply the changes. If the port does not have a link when you change the parameters, then the new parameters will be applied when the port becomes link up, and no soft reset is required.

The mention of “…reset service…to its Identity Object…” refers to how you would issue a soft reset after changing IP parameters. The Identity object is CIP object class code 0x01. Here is an extract from the CIP specification:

eee

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings