我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What is the dissipated heat loss of ATV630 process drives?

Issue:
Dissipated heat loss of the ATV630

Product Line:
Altivar 600 Process Drives

Environment:
All serial numbers for Altivar 600 Process Drives

Cause:
Cooling design

Resolution:

heat loss

What is the difference between forced cooled and natural area in power dissipation?
Forced cooled is cooling the heatsink by fan and natural cooled is the circuit board area without a fan. Sum of both is needed when a drive will be inside an enclosure.  Use values separately when using the flange kit to protrude the heatsink out the back of the enclosure and only the control parts are inside the enclosure.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings