What do I get an Error ID 2034 in Vijeo Designer?

Issue:

What do I get an Error ID 2034 in Vijeo Designer?

Product Line:

Vijeo Designer, HMI

Resolution:

Error ID 2034 is cause when the number of User Data Type exceeds 200.
Unfortunately there is no way to select All and Delete All. You will need to delete each User Data Type manually.

When exporting your Unity Variables you may want to unchecked DDT and or DFB. UDDT Dialog

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.