What is the maximum permitted distance between the 140ARI03010 and the sensor?
Issue:
What is the maximum permitted distance between the 140ARI03010 and the sensor?
Product Line:
140ARI03010
Resolution:
When using 3 or 4 wire RTD's the maximum distance between the module and the sensor is 200 meters.
If you're using 2 wire RTD's the distance is limited only by the user defined accuracy of the application.