Can you branch out from a variable to multiple function block input in Unity Pro?
Issue:
Can you branch out from a variable to multiple function block input in Unity Pro?
Product Line:
Unity Pro
Resolution:
Unity Pro does not allow branching out from a variable to multiple function block input pins. A viable work around would be to use the MOVE block and the output of the MOVE can be branched out to the inputs of the function blocks.