Video: How can an ATV630/ATV930 Process Drive be programmed to run using local keypad control?
Issue:
Can I program an ATV630/ATV930 process drive to run using local control?

Product Line:
ATV630, ATV930, Altivar Process

Resolution:




Programming Sequence

From the Main Menu:
  1. Scroll down (slide your finger around the wheel clockwise) to Menu 5 Complete Settings and press OK
  2. Then scroll down to Menu 5.5 Command and Reference, press OK, and verify/modify the following parameters:
  • config ref freq1= Ref.Freq-Rmt.Term               (sets the keypad to be your speed control)
  • control mode=  Separate                            (your start/stop command and speed reference are coming from different sources)
  • Command switching= Command channel 1    (tells the drive to look at channel 1 for start/stop)
  • CMD channel 1 = HMI                                     (tells the drive what command channel 1 is)

Note: If your drive is already set to I/O Profile  control mode, you can opt to leave that parameter set the way it is. As long as you have your reference and command channels programmed correctly, it won't matter what the
control mode is set to.
However, going from I/O Profile to Separate would force a factory reset. So if you're already set to I/O Profile, leave it in I/O Profile unless you want to do a factory reset.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings