Realflo is Not Recognizing Newly Added Flow Runs

Problem:

An activation code has been used to increase the number of flow runs on a SCADAPack controller (let's say from 2 runs to 4 runs) but I am unable to load a configuration for the new number of flow runs.

Solution:

After applying the activation code to the controller, you can verify the options on the controller by selecting Controller > Flow Computer Information
Flow computer information window showing four flow runs are now activated

4 runs now appear to be activated. Now, if you try to install a new configuration with 4 flow runs configured, you could get an error message indicating that only 2 runs are available. Older versions of Realflo did not give much information when this error occurred which could lead to some confusion. Realflo 6.95.1 will now give you the following error.

Communication Status window error "The requested number of flow runs cannot be configured"

When the flow computer was first loaded to the controller, it looked at the number of enabled flow runs and allocated enough memory to accommodate only that number of flow runs (in this example, 2 flow runs).

To get past this problem in Realflo Expert Mode, go to Configuration > Replace Flow Computer and reinstall the flow computer. Realflo may try and install the most recent version of flow computer and it is up to the user to determine if a previous version is more appropriate for their application.

By replacing/updating the flow computer, Realflo will again look at the number of currently enabled flow runs (now 4) and allocate enough memory to handle up to 4 flow runs. With the new flow computer installed, you should now be able to load your configuration with up to 4 flow runs.

Note: This solution applies to SCADAPack, SCADAPack 32 and SCADAPack 300-series and does not apply to SCADAPack x70 controllers.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings