Cannot log in to FlexNet Publisher in PME 8.2

Issue
User cannot log in to the FlexNet Publisher web interface in Power Monitoring Expert (PME) 8.2 and receives a “Password is incorrect” message, even when using known credentials.

Product Line
Power Monitoring Expert 8.2

Note: Legacy article. This behavior applies to the FlexNet Publisher licensing implementation used in PME 8.2.

Environment
FlexNet Publisher (lmadmin)
Power Monitoring Expert licensing

Cause
In PME 8.2, FlexNet Publisher user credentials may not function as expected due to changes in license server configuration or credential initialization. The FlexNet Publisher web interface and administrator account still exist, but access can fail if the stored credentials are invalid or corrupted.

Resolution
Warning: This procedure involves editing configuration files. Always back up files before making changes.

Use the following steps to reset the FlexNet Publisher administrator password:

  1. Navigate to:
    C:\ProgramData\Schneider Electric\Floating License Manager\FLEXnet Publisher License Server Manager\conf
  2. Open the server.xml file in a text editor.
  3. Locate the administrator entry and update the password value, for example:
    id="admin" lastName="Administrator" password="(ENC-01)AxlKxBaCLbp4iPFsjJ6eOFtE+qoJWH8ThHIKN9DgdEgILS9j" passwordExpired="false"
  4. Save the file.
  5. Restart the lmadminschneider service.
  6. Open a browser and navigate to:
    http://<SERVERNAME>:8090
  7. Click Administration and log in using:
    Username: admin
    Password: admin

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support Information

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings