How can I monitor health on the Local and IO Bus on a Control Expert (formerly Unity Pro) Momentum processor?
Issue:
How can I monitor health on the Local and IO Bus on a Control Expert (formerly Unity Pro) Momentum processor?
Product Line:
Control Expert, formerly Unity Pro, Momentum
Resolution:
%SW135 provides local bus health .
%SW128-129 provide I/O Bus health for up to 32 nodes.