我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to troubleshoot an ILF fault on an Altivar Process Drive?
Issue:
What is the cause of  ILF [Internal Link Error] fault on an Altivar Process Drive?

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
N/A

Resolution:

Cause
Communication interruption between option module and the drive.

Remedy
  • Verify connection to the proper slot
    • Slot A
      • Communication Modules (DeviceNet, Ethernet IP, Profibus, ProfiNet...)
      • I/O & Relay Module
    • Slot B
      • Encoder Card (Analog, Digital, Resolver...)
      • I/O & Relay Module
  • Verify the environment (electromagnetic compatibility)
  • If using Communication Module, check drives firmware version. (For most cases it should be at least V1.5IExx)
  • Save configuration file on keypad, remove option module and do a factory reset. If fault disappears then it might be a bad option module.
  • Replace the option module.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings