Are the PM8000 series meters capable of measuring earth leakage current?
Issue:
A customer would like to know if an earth leakage current measurement is available for the PM8000 series meters.
Product Line:
PM8000 series
Environment:
default measurements
Cause
Need to know if the PM8000 series meter is capable of measuring earth leakage current
Resolution:
The PM8000 has an output register called 'I5' in the Power Meter module which does precisely this. It calculates the instantaneous residual current from I1,2,3, and 4. Because it is treated like a real current channel, you can also capture waveforms and display harmonics from I5.
The caveat is that the wiring setup must have a CT on each line, I1, I2, and I3 (and I4 for 4-WYE). Otherwise your residual will include any current not measured directly by a CT.
Note:
I5 is calculated by: I5= I1 + I2 + I3 + I4
PM8000 series meter documentation.
發佈於: 施耐德電機Taiwan
需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。