我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What are the data types that are supported in Power monitoring Expert's Ecostruxure Web Services (EWS)?

Issue:

When attempting to read unsupported data types through EcoStruxure Web Services (EWS) in Power Monitoring Expert (PME), the following error may occur:

Couldn't convert value to double: double

Product Line:

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

EcoStruxure Web Services (EWS)

Environment:

EWS client applications

Cause:

EWS in PME supports only specific data types for measurement values. Attempting to read unsupported types (such as strings) results in conversion errors.

Resolution:

The following data types are supported in PME’s EWS interface:

  • Double
  • Boolean
  • DateTime

Note:

  • String data type is not supported in EWS for measurement values.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo-psup@se.com

support details

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings