How much memory does the PowerLogic PM8000 series meter have and what it is used for?

Article available in these languages:

Issue
How much memory does the PM8000 series have and what it is used for?

Product Line
PM8000 series

Environment
PM8000 on-board memory
PM8000 data log


Resolution
The 8000 series has 512 MB of memory which is used by the firmware and ION framework. However, this 512 MB of memory is not configurable by the end user. The user only has access to manage the logging memory, which is 10 MB in size, and the FTP site memory.  More information on the FTP site memory can be found in article FA317553 ION Setup can configure how the on-board logging memory is allocated through the Setup Assistant.


ION Setup Config Menu

The PM8000 series meter default logging framework is configured to record data and events at the following pre-defined intervals or conditions:

Data Recorder numberLog nameDepthInterval
1Revenue Log3360 (35 days)900 seconds (15 minutes)
9Loss Log3360 (35 days)900 seconds (15 minutes)
2, 3, 4Historic Logs3360 (35 days)900 seconds (15 minutes)
39Daily Nominal Logs450Triggered on Demand
7, 8Harmonics Logs840 (35 days)3600 seconds (1 hour)
N/AWaveform recorders (6 total)30Triggered on Demand
N/ACOMTRADE records10Triggered by waveform recording (if COMTRADE logging is enabled
10Energy/Demand (EgyDmd Log)3360 (35 days)900 seconds (15 minutes)
5Sag/Swell Log100Triggered on Demand
N/AEvent Log500Triggered on Demand
11, 12, 17, 19 - 26, 28, 29, 32, 35EN50160 LogsvariesEN50160 Interval
6, 16, 37, 38, 404-30 LogsvariesIEC61000-4-30 interval


The PM8000 series meter can support up to 50 data logs (data recorders) which can each record up to 16 different parameters.

The latest version of ION Setup can be downloaded from the link below.
ION Setup Latest Release | Schneider Electric

PM8000 frequently asked questions: FA244498

施耐德電機Taiwan

探索更多

系列:

探索更多

系列:

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。