Can the Analog Output power supply be deactivated to connect to an externally powered monitor device on altivar process drive?
Issue:
Can the Analog Output power supply be deactivated to connect to an externally powered monitor device on altivar process drive?

Product line:
Altivar Process, ATV600 ATV900

Environment:
All

Cause:
Needs to use an external power supply

Resolution:
The Altivar Process drives do not have a means to deactivate the power supply on the AQ1 or AQ2 terminals.  The customer will need to find an external device to convert the signal.