我们今天能为您提供什么帮助?

What are the considerations for PM3255 digital input and output ?

Issue

What are the considerations for PM3255 digital input and output?

Product Line

PowerLogic PM3000 Series (PM3255)

Environment

PM3255 Power Meter – Digital Inputs and Outputs

Resolution

  • The digital outputs of the PM3255 are polarity independent, meaning they do not require a specific polarity for proper operation.
  • The digital inputs and outputs of the PM3255 are electrically independent, so they function separately without electrical interaction between them.

施耐德電機Taiwan

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。