How to calculate and configure the Zero and Full scale value for a PM8000 Analog Input
Issue
Configuring the analog input on a PM8000.

Product Line
PM8000 series

Environment
Meter Configuration

Cause
Unlike other ION devices, the PM8000 analog input is only rated for 4-20mA rather than 0-20mA.

Resolution
Per the ION Reference, the Zero Scale can be calculated as follow:

Zero Scale = FullScale - (FullScale - X)(Af - Ax)/(Af - Aa)

where
Aais the analog hardware output minimum range value.(For the PM8000, Aa is equal to 4 mA.)
Afis the analog hardware output maximum range value.(For the PM8000, Af is equal to 20 mA.)
Axis the analog hardware output minimum value.(For the PM8000, Ax is equal to 4 mA.)
Xis the scaled equivalent of Aa.(This is determined by the device sending the Analog signal.)

The previous equation can be simplified to:

Zero Scale = FullScale - (FullScale - X)*(Af - Ax)/(Af - Aa)
Zero Scale = FullScale - (FullScale - X)*(20 mA - 4mA)/(20 mA - 4mA)
Zero Scale = FullScale - (FullScale - X)
Zero Scale = X

Therefore, the Zero Scale should correspond with the 4mA value.

For example, if a PM8000 meter is monitoring a 0 to 120 kW system and receiving the power information via a 4 - 20 mA analog signal, the PM8000 would need to be configured to have a Zero Scale of 0 and a Full Scale value of 120.

For instructions on programming the Zero Scale and Full Scale values, see attachment below.
Note: From firmware v3.0.0 the PM8000 has an optional Analog I/O (METSEPM890024) version 001.002.000 for 4-20 mA and 0-20 mA.

施耐德電機Taiwan

附件
Zero Scale and Full Scale values instructions.docx [75.93 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings