Dashboard functionality breaks after an in-place PME upgrade if Azzo gadgets are installed.

Issue:

After a PME in-place upgrade, the Dashboards web application may stop working when Azzo gadgets are installed.

Product Line:

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

PME Web Applications — Dashboards

Cause:

This issue can occur due to MSI component ownership/reference counting behavior affecting shared Dashboards platform files when upgrading PME with Azzo gadgets installed.

In PME 8.1, certain platform files required by Dashboards and Slideshow may have been placed in the following directories by an MSI package associated with Azzo components (because these files were not always deployed by the PME installer in that version):

  • ...\Power Monitoring Expert\Applications\Dashboards\bin
  • ...\Power Monitoring Expert\Applications\Slideshow\bin

At this stage, Dashboards and Azzo gadgets typically work because the required files exist.

During the upgrade, the installer is expected to deploy/update the platform files in those same locations. However, in some upgrade cases the installer may not refresh the expected files consistently. One observed indicator is ProductInfo.xml still pointing to the previous PME, leaving the Dashboards/Slideshow components in an inconsistent state.

After the upgrade, MSI reference counting can result in the platform files being removed or left mismatched, leading to missing dependencies in Dashboards and Slideshow.
As a result, Dashboards can fail to load or render properly because required files are missing from Dashboards\bin and Slideshow\bin.

Resolution:

Warning
Back up the system (or at minimum, the Dashboards and Slideshow folders) before modifying or replacing files.

  1. Recommended (Azzo package refresh)

    • Uninstall the existing Azzo diagnostics/gadgets package, then install the latest Azzo package compatible with PME.
    • To uninstall the existing Azzo package, re-run the previous installer used to install it and select Remove when prompted.
  2. Manual file recovery (if Dashboards/Slideshow bin files are missing)
    Ensure the following files exist in both locations:

    • ...\Power Monitoring Expert\Applications\Dashboards\bin
    • ...\Power Monitoring Expert\Applications\Slideshow\bin

    Required files:

    • Configuration.dat
    • Gadget.Data.dll
    • Internationalization.dll
    • Interop.Internationalization.dll
    • LicenseManager.Logic.dll
    • Licensing.LicenseManager.dll
    • ProductInfo.xml
    • SELMBrick.dll

    Copy missing files from a known-good system running the same PME version (8.2) or from the appropriate PME installation source/bin used by your deployment.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support information

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings