PME : Changing Database server name in PME product uninstaller

Issue
While attempting to run the PME product uninstaller, the user is unable to change the 'Database Server' name as the field is greyed out within the window.

uninstaller

Product Line
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023

Environment
PME Uninstaller

Cause
In a standalone/distributed system environment, the database instance server name may have been changed inadvertently without following the correct procedure for server name changes.

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

1. Navigate to the following directory: C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Uninst_PowerMonitoringExpert

2. Open the 'InstallInfo.xml' document in Notepad for editing.

3. Change the following parameters and point them to the current database server name.

- globalMachineName
- globalMachineFQDN
- globalEEMDBName
- globalEEMDbServer

Example:

globalMachineName="WTCALVSE010WYMD" globalMachineFQDN="WTCALVSE010WYMD.nam.gad.schneider-electric.com" globalEEMDBName="WTCALVSE010WYMD" globalEEMDbServer="WTCALVSE010WYMD"

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings