why can't I control my safety modules (red flickering ERR led on the I/O modules) when I start my application
Most likely, the safe communication is invalid. (see attached example screenshot)

- either the CPU is configured in NTP client mode, and NTP server is not present => in order to manage this situation,
-> use the safety device-DDT diag bits in the logic to warn if the NTP service is down :device DDT /S_COM_DBG/M_NTP_SYNC  and /S_COM_DBG/CPU_NTP_SYNC

- or, the CPU is configured in NTP server mode, but the safe communication is invalid => in order to revalidate the safety communication :
-> updated the real time clock of the CPU
-> set the process system word %SW128 to 16#1AE5 and then to 16#E51A .

important Note : when using a CPU that wasn't powered for a long time, prior to install it, it must anyway be powered, and the Real Time Clock must be set to present date & time using Unity Pro

Basics :
in order to deal with safety I/Os, a safety CPU and his remote I/O drop head (CRA) use their Real Time Clocks (RTC) to time stamp their safety exchanges, cross-checking the time stamps of his counterpart exchanges vs its own RTC in order to maintain the accuracy of their RTC, the CPU and CRA rely on the NTP protocol, and need a reachable NTP server.
if the NTP server is not reachable, then the RTC of each element (CPU and CRA(s)) are not updated, the safety communication synchro remains invalid, the safety communication remains invalid, and the I/O remain in fall back state.

施耐德電機Taiwan

附件
safe_com_device_ddt.zip [114.3 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings