Intermittent Communications to EM4800 in PME

Issue

The EM4800's communications are intermittent, despite the device consistently responding to network pings.

Product Line

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

EM4800

Cause

Network latency on the EM4800’s network segment is higher than expected. The default PME receive‑timeout value (10,000 ms) may be insufficient, causing intermittent communication drops.

Resolution

Increase the receive timeout for the EM4800 device:

  1. Open Management Console.
  2. Navigate to Devices and locate the EM4800.
  3. Right‑click the device and select Properties.
  4. In the Properties window, right‑click the white space and select Advanced Properties.
  5. Change Receive Timeout from 10,000 ms to 20,000 ms.
  6. Save and close.


Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com