Can you power up the ATV32 with an external 24Vdc supply?
Issue:
ATV32 power up with an external 24Vdc supply
Product Line:
ATV32
Environment:
All serial numbers
Cause:
To maintain control power to the drive.
Resolution:
Yes, the P24 terminal and COM are the connections that can be used for external 24VDC.
**NOTE: This does not apply to the ATV320, the P24 terminal on ATV320 is only used to supply the STO (Safe Torque Off) terminal, P24 will not accept 24v.