我们今天能为您提供什么帮助?

Video: Configuring MBP_MSTR Function Explicit Read Between Quantum 140CPU65160 PLC Native Ethernet Port & Other ModbusTCP Device

This procedure has been created with Unity Pro v12 software. It will cover the configuration and setup for the MBP_MSTR function block to perform an explicit read operation between the Quantum native ethernet port and another supported ModbusTCP device over ethernet.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings