Issue
Setting up the web viewer gadget to display real-time trends.

Product Line
Power Monitoring Expert 8.x

Environment
Power Monitoring Expert
Web Applications

Cause
The user requires the setup of real-time trends in dashboards.

Resolution
1. Log into PME Web Applications by navigating to (http://[SERVERNAME]/web) or using (http://localhost/web) directly from the server.
2. Click on the 'Trends' tab, and select one of the trends set within the Trends Library.
3. Right-click on the selected 'Trend' and select 'Open in New Window'.
PME 8.x: How to use the Web Viewer Gadget to display Real Time Trends

4. Copy the unique URL generated for this trend from the browser's URL address bar.
PME 8.x: How to use the Web Viewer Gadget to display Real Time Trends
5. Navigate to the 'Dashboards' tab and click on 'Edit Dashboards' within the Dashboard Controls section.
6. Click on 'Add Gadget' and select the 'Web Viewer' gadget.
7. Define a 'Title' within the 'Gadget Setup - General Settings' window and click Next.
8. Paste the unique trend URL from the clipboard to the 'Source' field, and select the 'Refresh Interval' and 'Display' preferences.
9. Click 'Finish' to save the Web Viewer gadget configuration.

Gadget Setup

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings