我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What is Power Consumption [kWh] register address of the TeSysT motor management system?
The base module LTMR can give you only current and time-related variables.  For reading voltage, energy or power-related variables it is necessary to add expansion module LTMEV40.. to your LTMR.
Register addresses can be found in LTMR – xxxx manual (where xxx is Modbus, canopen, profibus Ethernet or devicenet).
Except the canopen and devicenet that uses index/subindex or devicenet addressing, all the other communication uses the same logic addresses.
So if you open LTMR – Modbus manual, the list of registers starts on page 32 (with datatypes description), and the logical addresses 0-1399 are on pages 39-60

For reading the measurement we have to look into monitoring variables, to be precise to measuring variables, addresses 465 – 539.
However there is one exception.
The active and reactive power consumed is not in this group of measurement variables. They are in the group of “monitoring statistics” which are addresses between 122 and 149.
So active power consumption, with the unit 0.1kWh is situated on 2 addresses, 143 and 144. The value is stored as unsigned double integer, means 32-bit unsigned value. Reg 144 carries lower 16bits, reg 143 gives  higher 16 bits.
Manual being referred is DOCA0130EN-00, 07/2017

施耐德電機Taiwan

附件
FAQ.jpg [116.53 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings